Project overview

A fruit processing and cold-storage plant in southern Hungary wanted to cut its electricity costs by using every kilowatt-hour generated on site, without exporting any power to the public grid. The owner installed a 366 kWp rooftop PV system and a 300 kW / 711 kWh battery energy storage system (BESS), and turned to Hungarian BESS integrator BST Solar for control design, integration and commissioning. BST Solar built the system around a ComAp InteliNeo 5500 controller, which stores excess daytime solar generation to power the plant’s cooling and processing through the evening and night. The controller also enforces the strict no-export connection and manages reactive power from the plant’s compressors and motors, keeping the site within the utility’s power-factor limits.

Key objectives:

  • Maximise solar self-consumption while ensuring zero grid export
  • Maintain utility power-factor compliance and improve power quality
  • Automate energy management, with the ability to respond to external dispatch requests

The challenge

The site’s grid connection was subject to a self-consumption permit with reverse-power protection, so exporting electricity to the public grid was prohibited under all operating conditions.

The plant’s cooling compressors and processing motors also drew significant inductive reactive power. Moving outside the utility’s permitted power-factor range would bring financial penalties, yet the customer wanted to avoid investing in additional compensation equipment such as capacitor banks.

BST-Hungary-ComAp

The solution

BST Solar built the project around the InteliNeo 5500, which continuously measures active and reactive power at the grid connection point. The controller communicates over Modbus with the battery management system, three Delta PCS100HV power conversion systems, and a Huawei SmartLogger serving the site’s three Huawei PV inverters. Storage is provided by three CATL EnerOne+ battery cabinets.

Using ComAp’s built-in Import/Export Limitation function, the controller regulates battery charging and discharging so that the connection point stays at zero export, whatever the PV output or external operating requests.

The InteliNeo 5500 also handles reactive power compensation. By monitoring reactive power at the point of connection and using the storage inverters to offset the plant’s inductive load, it keeps site demand within the distribution system operator’s permitted power-factor range. ComAp's WebSupervisor provides remote monitoring of the whole installation.

ComAp Zero export Hungary 3

The result

The plant now uses its own solar generation with no risk of grid export. Excess daytime energy is stored in the battery and used after sunset, reducing the site’s reliance on purchased electricity.

Using the battery inverters for dynamic power-factor correction has removed the risk of reactive-power penalties without any additional compensation hardware. Operators can monitor system performance, alarms, and operating data remotely through WebSupervisor, and the automated control platform positions the site for future participation in flexibility markets.

ComAp Zero export Hungary

The battery and the ComAp control system let us use our own solar energy around the clock without any risk of exporting to the grid, and it even fixed our power factor. We can see exactly what the plant is doing at any time.

Josip Kovács, CEO, BST Solar

Our website uses cookies and similar technologies to provide you the best experience and to understand how you use our site.

You may either „Accept all“ by which you agree with using functional, analytical and marketing cookies. By pressing „Revoke“ only necessary cookies shall be allowed to enable the website and applications function correctly.. To revoke your consent you can do it from footer menu in Change cookie preferences section.